23.5: Transformers
- Page ID
- 89807
( \newcommand{\kernel}{\mathrm{null}\,}\)
The electric power generated in power stations is transmitted using high-voltage transmission lines, typically with voltages above 300000V for long distances. However, that voltage is not usable in our households, as our appliances expect a voltage around 120V (or \220V in Europe). Transformers use electromagnetic induction to transform one alternating voltage into another. Figure 23.5.1 illustrates a transformer.

The transformer has two coils, the “primary” and the “secondary”, with different numbers of loops, Np, and Ns, respectively. The coils are wrapped around an iron core, which can transmit the magnetic flux generated in the primary coil to the secondary coil. In the transformer, an alternating voltage, ΔVp, is applied to the primary coil, and transformed into the desired voltage, ΔVs, in the secondary coil.
The current in the primary coil creates a magnetic field. Those field lines are transmitted by the iron core into the second coil. A voltage is only induced in the secondary coil if the magnetic flux through the secondary coil changes with time. Thus, transformers only work with alternating voltages, so that the magnetic field created by the primary coil changes continuously. Both coils will have the same magnetic flux, ΦB, through them, since they have the same area. The voltage in the primary coil is given by Faraday’s Law:
ΔVp=NpdΦBdt
as is the voltage in the secondary coil:
ΔVs=NsdΦBdt
Since the flux (and thus its time-derivative) are the same in both coils, we can isolate the time-derivative in each equation to obtain the relationship between the voltages in the two coils:
ΔVpNp=ΔVsNs∴ΔVs=NpNsΔVp
Thus, with a transformer, one simply needs to set the ratio of the number of loops in each coil in order to transform one voltage into another.
Exercise 23.5.1
Which coil in Figure 23.5.1 has the highest voltage?
- The one with the most loops.
- The one with the least loops.
- Answer
-
Exercise 23.5.2
Which coil in Figure 23.5.1 will have the highest current?
- The one with the most loops.
- The one with the least loops.
- Not enough information to tell.
- Answer
-
Example 23.5.1
A power plant produces energy at rate of P=150kW, and wishes to transmit this power as efficiently as possible to a town. The power lines between the power plant and the town have a resistance of R=0.5Ω. Compare the amount of power dissipated in the transmission lines depending on whether the power is transmitted through a voltage of 300000V or 300V.
Solution
We model the transmission of power from the power plant to the town using the circuit shown in Figure 23.5.2.
We do not know the resistance of the town, but we can still calculate the power that is dissipated in the transmission lines that have a total resistance of R=0.5Ω. The power plant produces power, P, and transmits it through the lines at a potential difference, ΔV, resulting in a current, I:
P=IΔV∴I=PΔV
The current, I, will dissipate power in the lines at a rate of:
Pline=I2R=P2ΔV2R
With the two different voltages, this corresponds to:
Pline=P2ΔV2R=(150×103W)2(300000V)2(0.5Ω)=0.1WPline=P2ΔV2R=(150×103W)2(300V)2(0.5Ω)=125000W
Thus, when the power is transmitted at low voltage, more than 80% is dissipated in the transmission lines, whereas an insignificant fraction is dissipated when the power is transmitted at high voltage. This is why we need transformers.